Screw compressors are essential components of industrial refrigeration systems. They are widely used in cold storage facilities, food processing plants, seafood processing facilities, freezing production lines, and various other industrial applications.
During operation, screw compressors may experience problems such as high temperatures, abnormal pressure, excessive vibration, unusual noise, low oil pressure, or reduced refrigeration capacity. These symptoms may be related to the compressor itself, but they can also originate from the cooling system, electrical supply, refrigerant circuit, control system, or auxiliary equipment.
Recognizing the early warning signs of screw compressor failure enables businesses to carry out timely inspections, prevent further damage, and reduce the risk of production downtime.
However, a compressor should not be diagnosed as faulty based on a single symptom. A reliable diagnosis requires a combination of operating data, alarm codes, pressure readings, temperature measurements, and technical inspection results.
Under normal operating conditions, a screw compressor produces a certain level of mechanical noise and vibration. However, if the noise suddenly increases, metallic knocking sounds appear, a high-pitched squealing noise develops, or vibration becomes significantly stronger than usual, the system should be inspected.
Common warning signs include:
Unusual knocking or metallic impact sounds.
Increased vibration compared with normal operating levels.
Squealing noises coming from the motor, coupling, or auxiliary equipment.
Loose foundation bolts, mounting brackets, or connecting components.
Increased vibration accompanied by abnormal temperatures or pressures.
Abnormal vibration and noise can result from several factors, including:
Improper alignment between the motor and compressor.
Loose foundation bolts, machine bases, or mounting brackets.
Worn bearings or other mechanical components.
Unsuitable refrigerant flow or operating conditions.
Problems with the motor or auxiliary equipment.
The exact faulty component cannot be identified by sound alone. Vibration measurements, maintenance records, and the manufacturer's technical documentation should be reviewed to determine the underlying cause.
When severe knocking or a sudden increase in vibration occurs, assess the level of risk and shut down the equipment according to the applicable safety procedure when necessary.
Technicians may inspect the machine base, coupling, shaft alignment, mechanical connections, and vibration data. If internal compressor damage is suspected, a more detailed inspection should be performed in accordance with the manufacturer's instructions.
Do not continue operating the compressor merely to observe the problem when serious mechanical impact or abnormal vibration is present.
Operating temperature is an important indicator of screw compressor condition. If discharge temperature, oil temperature, or motor temperature exceeds the permitted limit, the system may generate an alarm or automatically shut down through its protective controls.
Common symptoms include:
Discharge temperature rising above normal operating levels.
Abnormally high oil temperature.
High-temperature alarms displayed on the controller.
Compressor shutdown triggered by thermal protection.
Reduced refrigeration capacity accompanied by rising temperatures.
Potential causes include:
High condensing temperature caused by inadequate heat rejection.
Low suction pressure or a compression ratio higher than expected.
Problems with the lubricating oil or oil cooling system.
Fouled heat exchangers or insufficient cooling-fluid flow.
Operation outside the manufacturer's permitted operating envelope.
Faulty temperature sensors or control-system inaccuracies.
Each compressor model has its own temperature limits and operating requirements. Therefore, operating conditions should be checked against the manufacturer's technical documentation rather than a universal temperature threshold.
First, check the controller alarms and identify which operating parameter has exceeded its limit. Next, evaluate the heat-rejection system, operating pressures, oil system, and associated equipment.
If the compressor has shut down because of thermal protection, do not repeatedly restart it before identifying the cause. Ignoring the alarm may allow the equipment to continue operating under unsafe conditions.
Suction and discharge pressures indicate the operating condition of a refrigeration system. When these values deviate significantly from design conditions or normal operating records, an investigation is necessary.
Possible symptoms include:
Suction pressure lower than expected.
Abnormally high suction pressure under certain load conditions.
Excessively high discharge pressure.
Differential pressure inconsistent with operating requirements.
Inability to achieve the required refrigeration capacity.
| Symptom | Potential Causes to Investigate |
|---|---|
| Low suction pressure | Low refrigeration load, insufficient refrigerant charge, restricted refrigerant flow, or evaporator-related problems |
| Abnormally high suction pressure | Increased refrigeration load, changing evaporating conditions, or improper capacity control |
| High discharge pressure | Poor condenser heat rejection, high ambient temperature, or unsuitable operating conditions |
| Continuously fluctuating pressure | Variable load, unstable control, refrigerant supply problems, or auxiliary equipment faults |
The table above lists common possibilities for initial investigation. The same symptom may have several different causes depending on the system configuration.
Technicians should record suction pressure, discharge pressure, corresponding temperatures, and the system load at the time the problem occurs. These readings should then be compared with design specifications and historical operating data.
The evaporator, condenser, control valves, piping, and refrigerant supply should also be inspected before concluding that the compressor itself is faulty.
For systems using ammonia (NH3/R717), all inspections must be performed by trained personnel using suitable equipment and following established ammonia safety procedures.
Reduced refrigeration capacity can directly affect production operations. Businesses may observe the following symptoms:
Cold storage rooms struggle to reach their set temperatures.
Cooling or freezing cycles take longer than usual.
Product temperatures fail to meet required specifications.
The compressor runs for extended periods but provides insufficient cooling.
Other refrigeration equipment must operate longer or more frequently to meet the load.
Low refrigeration capacity does not necessarily mean that the compressor is damaged. Possible causes include:
Actual refrigeration load exceeding the system's design capacity.
Fouled evaporator coils or poor heat transfer.
Insufficient refrigerant flow.
Unsuitable suction and discharge pressure conditions.
Malfunctioning compressor capacity-control mechanisms.
Refrigerant leaks or inefficient auxiliary equipment.
Evaluate the entire refrigeration system before deciding to repair or replace the compressor. Check the refrigeration load, room temperature, evaporator condition, condensing conditions, and compressor capacity-control operation.
If operating data indicates that the compressor is not delivering the performance specified by the manufacturer, technicians can conduct a more detailed assessment of the capacity-control mechanism, mechanical condition, and internal components.
If a refrigeration system consumes more electricity than usual without a corresponding increase in cooling output, businesses should investigate the operating efficiency of the compressor and associated equipment.
Possible symptoms include:
Increased electrical power consumption under comparable load conditions.
Abnormally high motor current.
Extended compressor operating hours.
Rising electricity costs while product temperatures remain difficult to control.
Simultaneous temperature or pressure alarms.
Higher electricity consumption may be associated with:
High condensing pressure.
An evaporating temperature lower than required.
Increased refrigeration load or extended operating hours.
Reduced heat-exchanger performance.
Improper capacity control or system settings.
Problems with the motor or mechanical components.
Electricity consumption should be compared under equivalent load and temperature conditions. Without controlling for these factors, comparisons between different days or production shifts may lead to incorrect conclusions.
Monitor electrical power, motor current, suction pressure, discharge pressure, operating temperatures, and compressor running time together. These data help distinguish between increased consumption caused by production demand, ambient conditions, and declining equipment efficiency.
A compressor should not be replaced solely because electricity bills have increased. The underlying cause must first be identified, and the energy performance of the entire refrigeration system should be evaluated.
In oil-injected screw compressors, the oil system provides lubrication and supports sealing and heat removal, depending on the equipment design. Oil system failures can affect compressor reliability and service life.
However, oil system configurations vary by compressor model and design principle. The manufacturer's documentation should be consulted to establish the correct operating requirements.
Low oil pressure alarms.
Differential oil pressure below the required level.
Abnormally high oil temperature.
Oil level or oil quality outside the specified requirements.
Compressor shutdown triggered by oil system protection.
Potential causes include:
Incorrect oil level.
A clogged oil filter or excessive filter differential pressure.
Malfunctioning oil pumps or oil-control devices.
Oil that does not meet the manufacturer's specifications.
Faulty pressure sensors or measuring instruments.
When an oil-related alarm occurs, follow the shutdown and inspection procedures specified for the particular compressor model. Do not bypass protective switches or continue operating the compressor before the cause has been identified.
Industrial refrigeration compressors may be equipped with monitoring and protection systems designed to detect abnormal operating conditions. Depending on the configuration, alarms may relate to:
High discharge temperature.
High discharge pressure.
Low oil pressure.
Motor overload.
High motor temperature.
Sensor faults or control-system malfunctions.
When the compressor shuts down because of an alarm, record the alarm code and operating parameters at the time of the event. Repeatedly restarting the compressor without addressing the underlying problem can increase the risk of equipment damage.
Technicians should consult the manufacturer's alarm documentation, inspect the relevant operating conditions, and return the equipment to service only after all applicable safety requirements have been satisfied.
If the same alarm repeatedly occurs, a detailed diagnostic investigation is necessary rather than simply clearing the fault from the controller.
| Warning Sign | Potential Causes | Initial Inspection |
|---|---|---|
| Increased vibration or noise | Coupling, foundation, bearings, or operating conditions | Record vibration levels, inspect mechanical connections, and review maintenance records |
| High discharge temperature | High compression ratio, poor heat rejection, or operation outside permitted limits | Check temperatures, pressures, and the heat-rejection system |
| Low suction pressure | Low load, restricted refrigerant flow, or evaporator problems | Compare pressure readings with operating load conditions |
| High discharge pressure | Poor condenser heat rejection or abnormal condensing conditions | Inspect the condenser system and ambient temperature |
| Reduced refrigeration capacity | Excessive load, poor heat transfer, or capacity-control problems | Evaluate the entire refrigeration cycle |
| Increased electricity consumption | High operating pressures, increased load, or reduced efficiency | Compare energy consumption under equivalent operating conditions |
| Low oil pressure | Oil level, filter, oil pump, or measuring-device problems | Inspect according to the manufacturer's procedures |
| Frequent compressor shutdowns | Protective alarms, electrical supply, or control-system faults | Record alarm codes and investigate the underlying cause |
This table supports preliminary troubleshooting but does not replace professional diagnosis and repair procedures.
To reduce troubleshooting errors, businesses should establish a clear inspection and response procedure.
Step 1: Record the symptoms. Document the time of the incident, unusual noise, vibration levels, temperatures, pressures, and controller alarm codes.
Step 2: Assess the level of danger. If severe mechanical knocking, smoke, a burning smell, refrigerant leakage, or a critical protective alarm is detected, shut down the equipment in accordance with the applicable safety procedure.
Step 3: Review operating data. Compare actual measurements with permitted operating limits and historical equipment performance.
Step 4: Inspect associated equipment. Evaluate the electrical supply, heat-rejection system, oil system, evaporator, condenser, and control devices in accordance with technical instructions.
Step 5: Identify the root cause. Reach a diagnosis only after collecting sufficient operating data and obtaining appropriate inspection results.
Step 6: Perform repairs. All work must be carried out by qualified personnel using suitable replacement parts and following the manufacturer's documentation.
Step 7: Verify the system before restarting. Confirm safe operating conditions, protective functions, operating parameters, and commissioning or test-run results according to the approved procedure.
Ammonia (NH3/R717) is a toxic refrigerant that can cause serious harm if released. If an ammonia leak is suspected, do not enter the hazardous area to inspect or repair the system yourself. Activate the facility's emergency response procedure, warn people in the surrounding area, and allow trained emergency personnel to manage the incident in accordance with applicable safety requirements.
Do not open piping, dismantle equipment, or perform work that could expose personnel to refrigerant until the system has been isolated and the required safe conditions have been verified under an approved procedure.
Proactive maintenance helps identify abnormal conditions before they develop into serious equipment failures. The specific maintenance schedule should be based on the manufacturer's recommendations, operating conditions, and equipment maintenance history.
Important preventive measures include:
Regularly monitor suction pressure, discharge pressure, and operating temperatures.
Record motor current, electrical power consumption, and compressor running hours.
Inspect the oil system according to the equipment configuration and manufacturer's requirements.
Monitor vibration and noise to identify unusual changes.
Inspect evaporator and condenser heat-transfer performance.
Check protective devices, sensors, and control systems.
Maintain records of maintenance activities, alarm codes, and repairs.
Use replacement parts and consumables that meet the manufacturer's specifications.
Train operating personnel to recognize alarms and follow the correct shutdown procedures.
For continuously operating refrigeration systems, collecting operating data over time helps identify declining performance trends and supports more effective maintenance planning.
When a screw compressor exhibits abnormal operating symptoms, businesses should identify the underlying cause before deciding whether to repair the equipment, replace components, or invest in a new system.
Cong Nghiep BA can be introduced in this article as a point of contact for discussing industrial refrigeration system solutions, subject to verification of the services the company actually provides. Before publication, the stated service scope should be checked to ensure that it accurately reflects the company's technical capabilities.
To support the initial assessment, businesses should prepare the following information:
Compressor manufacturer and model.
Type of refrigerant used.
Operating hours and maintenance history.
Alarm codes or descriptions of abnormal symptoms.
Recorded pressure, temperature, and electrical current readings.
Photographs of the equipment and installation area, where they can be obtained safely.
Complete information helps technicians make a more accurate preliminary assessment and determine the appropriate next steps for inspection.
Common warning signs include abnormal vibration or noise, high operating temperatures, unusual pressure readings, reduced refrigeration capacity, increased electricity consumption, and frequent protective shutdowns. Inspection is required to determine the actual cause.
Possible causes include high condensing temperature, an excessive compression ratio, inadequate heat rejection, oil system problems, or operation outside the permitted operating range. Actual operating data should be compared with the technical documentation for the specific compressor model.
No. Low suction pressure may result from low refrigeration load, restricted refrigerant flow, evaporator conditions, or other system-related problems. The compressor should not be diagnosed as faulty based on this measurement alone.
Record the alarm codes and operating parameters at the time of shutdown, then investigate the underlying cause according to the manufacturer's instructions. Do not repeatedly restart the compressor or disable protective functions before the problem has been identified and corrected.
Advanced diagnostics, mechanical disassembly, and refrigerant-system repairs should be performed by qualified personnel with appropriate equipment. Operators should limit their actions to observations and measurements permitted by the facility's procedures.
Follow the manufacturer's maintenance schedule, monitor operating parameters, inspect the oil and heat-rejection systems, respond to alarms according to established procedures, and maintain detailed operating records. Preventive maintenance helps identify abnormal trends early and reduces the risk of unplanned shutdowns.
Recognizing the early warning signs of screw compressor failure is an important part of managing industrial refrigeration systems. Abnormal vibration, unusual noise, high temperatures, irregular pressures, reduced refrigeration capacity, and protective alarms are all conditions that require timely investigation.
However, these symptoms do not always originate from the compressor itself. Inspecting the entire refrigeration system, comparing operating parameters with the manufacturer's specifications, and identifying the root cause help businesses select appropriate corrective measures, control repair costs, and minimize production downtime.
In addition to addressing existing problems, businesses should maintain a preventive maintenance program, monitor operating data, and train personnel to improve the reliability of their industrial refrigeration systems.